20
20
Features
• Selectable digital display indicates either
setpoint or room temperature
• Automatic heat/cool changeover via
remote sensor
• Control depending on room/return
air temperature
• Three-speed fan switch
• Operating mode changeover input for
day/night temperature settings for energy
conservation
• Operating modes: normal, night setback
freeze protection or standby
• Selectable control parameters for:
– Independently adjustable night cooling or
night heating setpoints
– Minimum/maximum electronic limit stops
– Adjustable heating/cooling changeover
switch point
– Sensor calibration
– Adjustable Free Energy Band™ for
four-pipe model
– Adjustable switching differentials for
digital outputs or proportional band
adjustment for modulating outputs
– Minimum/maximum output on/off time
for compressor protection
– Fan overrun
Submittal Summary
Fan Coil Unit
RDF... Series Fan Coil Unit Controllers
Part Number 2-pipe 4-pipe Electric Control Valve Valve
Heat Output Action Actuator
RDF10U • On/off NO or NC SFP11U
SFA11U
RDF20U • • On/off NO or NC SFP11U
SFA11U
RDF30U • On/off Heat NO or NC SFP11U
Cool NC SFA11U
RDF50.1U • 0-10 Vdc NC SFA61
RDF60.1U • 3P NO or NC SSA81
Applications Matrix
Microprocessor-
based room
controllers with
digital display
are designed for
use in heating or
cooling only and
heating and
cooling (two-pipe
or four-pipe) fan
coil systems.